I. Overview
The RM6-12 Gas-Insulated Switchgear is a fully-insulated, hermetically-sealed SF6 metal-enclosed ring main unit (RMU) designed for 10kV medium-voltage distribution systems. Certified by the National High-Voltage Apparatus Testing Center and recognized as a Zhejiang High-Tech Product, it excels in reliability, modularity, and environmental adaptability. Widely used in urban/rural power distribution, industrial/commercial facilities, and renewable energy projects, it provides safe, efficient, and maintenance-free power distribution solutions.
Item | Unit | C Module | F Module | V Module | CB Module | ||
(Load Switch) | (Combined Apparatus) | (Vacuum Switch) | Isolation/ Earthing Switch |
(Vacuum Circuit Breaker) | Isolation/ Earthing Switch |
||
Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequency Withstand Voltage (PhasetoPhase / Port) | kV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
Lightning Impulse Withstand Voltage | kV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | Note ¹ | 630 | 1250/630 | 1450 | |
Breaking Capability | |||||||
Rated Loop Breaking Current | A | 630 | |||||
Rated Cable Charging Breaking Current | A | 10 | |||||
Rated ShortCircuit Making Current (Peak) | A | 50 | |||||
Rated Peak Withstand Current | kA | 50 | 80 | ||||
Rated ShortTime Withstand Current | kA/35 | 20 | 20 | ||||
Rated ShortCircuit Breaking Current | kA | 31.5 | 20 | 25 | |||
Rated Transfer Current | A | 1700 | |||||
Maximum Current of Equipped Fuse | A | 125 | |||||
Loop Resistance | μΩ | ≤ 300 | ≤ 600 | ||||
Mechanical Life | Times | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 |
Note ¹:Depends on the current rating of the fuse |